• Type : Ultraviolet and Infrared, Hydrogen flame detector • Detection Range : 100ft(30m) for n-Heptane fire 15ft(4.5m) for Hydrogen (30" plume) • Field of View : Horizontal 90°, Vertical 90° • Temperature Range Operating : -40℃ to +75℃ • Storage : -50℃ to +80℃ • Humidity Range : 0 to 95% relative humidity • Explosion proof : › Class I Division 1 Groups B,C and D(FM) › Class II Division 1 Groups E,F and G(FM) › Class III (FM) › Ex d IIB+H2, T6(ATEX) • Output › Relay - Fire Alarm, Fault Alarm, Warning Alarm - From A or B Selectable, 28vdc, 2A › 4-20mA › RS-485


• Dimensions (body) : W134 x H117 x D120 mm W5.3 x H4.6 x D4.7Inch • Enclosure Material : Stainless steel 316 • Shipping Weight : 3.4 kg (with Bracket) • Color : Metal • Conduit Entry Size : 2 X 1/2 inch NPT, M20 X 1.5


• Operating Voltage : Typical DC24V (17 to 32). • Power Consumption : 1.8W maximum at 32 vdc • Wiring : 14AWG(2.08mm2) to 24AWG(0.205mm2) shielded cable recommended. • Electromagnetic Compatibility : EMC Protected


 








RFD-2FTN-NEW

RFD-2FT5-I

RFD-2000X

RFD-2000X-H

RFD-2TN